We thinks what clients think, the urgency of urgency to act from the interests of a client position of theory, allowing for greater quality, lessen processing costs, price ranges are much more reasonable, won the new and outdated shoppers the support and affirmation for Ultra Filtration Process , Uf Membrane , Microfiltration System , And we can help looking for any products of the customers' needs. Make sure provide whole heartedly service, the high quality, The fast Delivery.
Manufacturer of Membrane Process - UF Membrane Module PVC Ultrafiltration Membrane Module UFc4040 RO housing – Bangmo Detail:
Applications
Production of mineral water, spring water, or other sterile liquid.
Drinking treatment of tap water, surface water, well water and river water.
Pretreatment of RO.
Treatment, recycle and reuse of industrial waste water.
Filtration Performance
This product is proven to have below filtering effects according to the service conditions of different water sources:
Ingredient |
Effect |
SS, Particles > 1μm |
Removal Rate ≥ 99% |
SDI |
≤ 3 |
Bacteria, Viruses |
> 4 log |
Turbidity |
<0. 1NTU |
TOC |
Removal Rate: 0-25% |
*Above data is obtained under the condition that feeding water turbidity is < 15NTU. This product is qualified for drinking water related products.
Product Parameters

Technical Parameters
Filtering Type |
Inside-out |
Membrane Material |
Modified PVC |
MWCO |
100K Dalton |
Membrane Area |
3.8m2 |
Membrane ID/OD |
1.0mm/1.8mm |
Dimensions |
Φ90mm*1016mm |
Connector Size |
Φ19mm |
Application Data
Pure Water Flux |
1,200L/H (0.15MPa, 25C) |
Designed Flux |
35-100L/m2.hr (0.15MPa, 25C) |
Suggested Working Pressure |
≤ 0.2MPa |
Maximum Transmembrane Pressure |
0.2MPa |
Maximum Working Temperature |
45C |
PH Range |
Working: 4-10; Washing: 2-12 |
Operating Mode |
Cross-flow or Dead-end |
Feeding Water Requirements
Before feeding water, a security filter < 50 μm should be set to prevent blockage caused by large particles in raw water.
Turbidity |
≤ 15NTU |
Oil & Grease |
≤ 2mg/L |
SS |
≤ 20mg/L |
Total Iron |
≤ 1mg/L |
Continuous Residual Chlorine |
≤ 5ppm |
COD |
Suggested ≤ 500mg/L |
*Material of UF membrane is polymer organic plastic, there must not be any organic solvents in raw water.
Operating Parameters
Maximum Backwashing Pressure |
0.2MPa |
Backwashing Flow Rate |
100-150L/m2.hr |
Backwashing Frequency |
Every 30-60min. |
Backwashing Duration |
30-60s |
CEB Frequency |
0-4 times per day |
CEB Duration |
5-10min. |
CIP Frequency |
Every 1-3 months |
Washing Chemicals: |
Sterilization |
15ppm Sodium Hypochlorite |
Organic Pollution Washing |
0.2% Sodium Hypochlorite + 0.1% Sodium Hydroxide |
Inorganic Pollution Washing |
1-2% Citric Acid/0.2% Hydrochloric Acid |
Component Material
Component |
Material |
Membrane |
Modified PVC |
Sealing |
Epoxy Resins |
Housing |
UPVC |
Product detail pictures:
Related Product Guide:
We have now a skilled, performance group to offer excellent support for our consumer. We usually follow the tenet of customer-oriented, details-focused for Manufacturer of Membrane Process - UF Membrane Module PVC Ultrafiltration Membrane Module UFc4040 RO housing – Bangmo , The product will supply to all over the world, such as: Uganda, Norwegian, Guatemala, We hope to have long-term cooperation relationships with our clients. If you are interested in any of our products, please do not hesitate to send enquiry to us/company name. We ensure that you can be totally satisfied with satisfactory solutions!